Products

Potter PS120 Pressure Switch

Potter PS120 Pressure Switch

Pressostat Potter PS120

Supervisory Pressure Switch for Excess Pressure Systems. Designed to detect an increase and/or decrease from normal system pressure in automatic fire sprinkler systems. Typical applications are: Wet pipe systems with excess pressure, pressure tanks, air supplies, and water supplies.

The PS120 switch is factory set for 120 PSI (8,3 BAR) normal system pressure. The switch marked with the word LOW is set to operate at a pressure decrease of 10 PSI (0,7 BAR) at 110 PSI (7,6 BAR). The switch marked with the word HIGH is set to operate at a pressure increase of 10 PSI (0,7 BAR) at 130 PSI (9 BAR).

Pressostat de surveillance pour systèmes de surpression. Conçu pour détecter une augmentation et/ou une diminution de la pression normale du système dans les systèmes de gicleurs automatiques. Les applications typiques sont : les systèmes de tuyauterie humide avec surpression, les réservoirs sous pression, les alimentations en air et en eau.

Le commutateur PS120 est réglé en usine pour une pression normale du système de 120 PSI (8,3 BAR). Le commutateur marqué du mot LOW est réglé pour fonctionner à une diminution de pression de 10 PSI (0,7 BAR) à 110 PSI (7,6 BAR). Le commutateur marqué du mot HIGH est réglé pour fonctionner à une augmentation de pression de 10 PSI (0,7 BAR) à 130 PSI (9 BAR).

Part#Potter#Switch / interrupteur
4071120PS120-1ASingle / célibataire
4071120 – 2APS120-2ADouble