Switch – Supervisory, Retrofit
Potter Flow
- Designed to monitor the fully open position of a ball valve installed in a sprinkler system
- Will fit on most ball valves installed on back-flow-preventers and alarm trim lines of dry, alarm, and deluge sprinkler valves
- Operates if the ball valve handle is moved from the open position
- The switch does not track the position of the handle or ball
- When the ball valve handle is in the open position, a spring-loaded switch button will contact the valve handle
- When the handle is moved from the open position, this switch button extends to the tripped position, and the RBVS-T contacts change state, thereby opening or closing a circuit
- The cover tamper switch is activated by the removal of the RBVS-T housing cover
- If an attempt is made to remove the RBVS-T by the removal of the mounting brackets, the unit will be set into the tripped mode by this action
- Waterflow Alarm Switch with Retard for Supervision of Wet Alarm Check Valve
Part# | Potter# |
---|---|
404077 | RBVS-T |
Additional Files
Click on the buttons inside the tabbed menu:
Sales Sheets
Other Documents
Switch – Supervisory, Plug Type
Potter Flow
- The Model PTS-C is designed to supervise sprinkler system control valves and may also be used to secure gates and other applications
- Useful for unusual conditions, such as non-rising stem valves
- Nema 6P enclosure allows the device to be mounted outdoors, even in areas subject to flooding such as pits and wells
- Sealed reed switch operation virtually eliminates contact corrosion
- Turning the valve wheel will pull the plug out of the receptacle
- The plug cannot be reinserted after operation until the plug receptacle cover is removed with the special hex key provided
Part# | Potter# |
---|---|
404074 | PTS-C |
Additional Files
Click on the buttons inside the tabbed menu:
Sales Sheets
Other Documents
Switch – Supervisory, OS & Y
Potter Flow
- The OSYSU is used to monitor the open position of an OS & Y (outside screw and yoke) type gate valve
- Mounts conveniently to most OS & Y valves ranging in size from 2” to 12” (50mm to 300mm. They will mount on some valves as small as 1/2” (12.5mm)
- The cover is held in place by two tamper resistant screws
Part# | Potter# | Switch |
---|---|---|
404070 | OSYSU – 1 | Single |
404072 | OSYSU – 2 | Double |
Additional Files
Click on the buttons inside the tabbed menu:
Other Documents
Switch – Supervisory, Control Valve
Potter Flow
- Weather proof and tamper resistant switch for monitoring the open position of fire sprinkler control valves of the post indicator, butterfly and other types
- Two SPDT (Form C) contacts are provided which will operate when the valve position is altered from an open state
- Mounts in 1/2” NPT Tapped hole in the post indicator or butterfly valve housing
- The device is engaged by the indicating assembly of the post indicator or the operating mechanism of the butterfly valve, actuating switch(es) when the valve is fully open
- Should be installed where it is accessible for service
- The cover is held in place by two tamper resistant screws
Part# | Potter# |
---|---|
404073 | PCVS-2 |
Additional Files
Click on the buttons inside the tabbed menu:
Sales Sheets
Other Documents
Switch – Flow Vane
Potter Flow
- ULC Listed and FM Approved for use on steel pipe; schedules 10 through 40, sizes 2” through 8” ( 50mm through 200mm)
- For use on wet sprinkler systems
- Enclosed in a general purpose, diecast housing
- Cover is held in place with two tamper resistant screws that require a special key for removal (included)
Part# | Potter# | Size |
---|---|---|
4070200 | VSR-S | 2” |
4070212 | VSR-2-1/2 | 2-1/2” |
4070300 | VSR-3 | 3” |
4070312 | VSR-3-1/2 | 3-1/2” |
4070400 | VSR-4 | 4” |
4070500 | VSR-5 | 5” |
4070600 | VSR-6 | 6” |
4070800 | VSR-8 | 8” |
40701000 | VSR-10 | 10” |
Additional Files
Click on the buttons inside the tabbed menu:
Sales Sheets
Other Documents
Switch – Vane Type Waterflow with Retard
Potter Flow
- For use on wet sprinkler systems that use 1 (25mm), 1-1/4” (32mm), 1-1/2” (38mm) or 2” (50mm) pipe size
- May also be used as a sectional waterflow detector on large systems
- Contains two single pole double throw snap action switches and an adjustable, instantly recycling pneumatic retard
- The switches are actuated when a flow of 8-10 gallons per minute (30-38 LPM) or more occurs downstream of the device
- Cover is held in place with two tamper resistant screws that require a special key for removal (included)
- Conduit Entrances: Two knockouts provided for 1/2” conduit
- Usage: Listed plastic, copper and schedule 40 iron pipe
- UL, ULC Listed
Part# | Potter# | Size |
---|---|---|
4070112 | VSR-S | 1”-2” |
Additional Files
Click on the buttons inside the tabbed menu:
Sales Sheets
Other Documents
Twine – Nylon Seine
- 275' of #18, 170 lb. Test for plumb line, seine line, fishing line, chalk line, mason line and lead line
- To stop fraying when cut, apply flame to cut end (nylon melts)
Part# |
---|
4115 |
Cable Ties
- Nylon Cable Ties can be used in countless applications, are adaptable to any environment and can be used both inside and outdoors
- LynCar cable ties are made with a one piece construction to provide consistent performance and reliability
- UV Resistant
Part# | Size |
---|---|
877 | 7-1/2” |
8711 | 11” |
8714 | 14” |
8721 | 21” |
Mineral Wool MW-300
- Pre-cut strips for easy installation
- Excellent sound deadening and insulation valve
- 4.5pcf (72kg/m3) density
- Tested at positive pressure to simulate the pressure differentials that can occur in a fire situation
Part# | Size |
---|---|
50653 | 3” x 4” |
Additional Files
Click on the buttons inside the tabbed menu:
Techanical Informaiton
Other Documents
Firestop – Collar – SSC Ring
- Pre-fabricated collar designed to seal combustible pipe penetrations in fire rated walls and floors
- 100% Intumescent silicone
- Low profile for hard to fit angles
- Expands to close penetrations
- Tested at positive pressure to simulate the pressure differentials that can occur in a fire situation
FBC™ System Compatible indicates that this product has been tested, and is monitored on an ongoing basis, to assure its chemical compatibility with FlowGuard Gold®, BlazeMaster® and Corzan® piping systems and products made with TempRite® Technology. The FBC System Compatible Logo, FBC™, FlowGuard Gold®, BlazeMaster®, Corzan®, and TempRite® are trademarks of Lubrizol Advanced Materials, Inc. or its affiliates.
Part# | Size |
---|---|
5065112 | 1½” |
5065200 | 2” |
5065300 | 3” |
5065400 | 4” |
5065600 | 6” |
Additional Files
Click on the buttons inside the tabbed menu: